                            RAMS of a Vital Input Card 
                              CHAPTER -1   
  Introduction  
 For a Railway Signal Interlocking system, Field Input conditions to be monitored by the Interlocking equipment are Track Cct / Axle Counter, Point Detection, Signal Aspect Proving, Level Crossing Gate, Crank Handle and Panel Buttons. The monitoring is done by reading the  Pick-up or Drop contacts  of corresponding Relays. 
 This could have been done by operating a Transistor through external Voltage fed via the pick-up Contact of the Relay. The Output of Transistor is processed by the Logic Solver ( Processor). But in that case,  there would be no Isolation  between external Analog Input and internal Digital Output circuits. An Opto Coupler is used for this purpose, where the Input LED and Output Phototransistor are  electrically isolated . The Input through Pick-up contact of Relay operates the LED of the Opto Coupler, light from which turns the output Phototransistor. The  interfacing using a Transistor and an Opto coupler is showed in Fig 1(a)&(b) 
   
 When the Relay is in Pick-up condition, the Transistor is Forward biased and  Collector Output to Processor is ‘0’ . During Drop condition of the Relay,  Collector Output is ‘1’ . 
 Input Interface Card converts the Analog information of DC Voltage fed through the Relay contacts to send TTL level to Processor. The basic features of the Card are: 
 
 All Inputs are fed through Opto Couplers having a  minimum Isolation Voltage of 1500V.     
 All Inputs are protected from Transient Voltages and Surges by using  Varistors.  
 
 
 To reduce Single-point Failure, both  Front and Back   potential-free  contacts of each external Relay are interfaced. They are read through different Ports and Bits to avoid common-mode failure. 
 
 
 Each Card gets  Hardware Address  of the particular Slot of the Backplane, to which it is inserted. This  Address must be matched with the Software Address  sent by Logic Solver Card before the external Relay Inputs are read. 
 
 
 Input Cards can be inserted or extracted with System Power-ON conditions.  A special circuit  is used to prevent transient to Stable +5V Supply to ICs, 
 
 
 Input data are read  employing Input Toggle  by the logic Solver or using multiple sets of Opto Couplers ensuring Hardware redundancy. 
 
 The Input Data Structure of the Interlocking System Inputs is given in Fig 2: 
   
 Panel Buttons and Keys are called Non-Vital Inputs and a Non-Vital Input / Output Card is used to read  32 Inputs . All other Inputs are Vital Inputs and a Vital Input Card reads  16 Relay Inputs.    
  A detailed diagram is showed in Fig  3 . Since Railway Interlocking is a  Safety-critical  System,  Inputs from both Pick-up and Drop Contacts  of a Relay is analysed. 
   
 Each Input is monitored by Opto Couplers by supplying Current from an  Isolated 12V Supply . 
 The Input to Processor will be ‘ 01’ in Drop Condition  and ‘ 10’ in Pick up Condition . These two combinations are  Valid Inputs . Other two Inputs ‘ 00’  and ‘ 11’  are  Invalid  and Processor will show Fault. But  during transition of Relay  between  Drop to Pick-up  or  Pick- up to Drop , both the  Opto Couplers will be OFF . So, Output will be  ‘11’ , which is Invalid 
 A  De-bouncing circuit  (U1) is used for feeding  steady Input  to the Logic Solver. In this case, during transition of Relay, the Input to Processor will remain  unchanged from Last State.   
 When the  Relay X is not operated , current flows through the  Drop Contact , Inductor, L1, Current Limiter R1, Resistor R2 and input Diode of Opto Coupler OC1. The Opto Coupler conducts and a level ‘ 0 ’ is fed to  Pin1 of U1 . This makes output  Pin 3 of U1   as ‘ 1 ’. At the same time, since no current passes through Input Diode of OC2, it does not  conduct. Level  ‘1’  is fed to   Pin 5 of U1  and output   Pin 6 of U1  to Port becomes  ‘0’.  
 Thus we get a pattern  0101  at the Port. 
 When the  Relay X is operated , current flows through the  Pick-up Contact ,  Inductor L2,  Current Limiter R5, Resistor R6 and input Diode of Opto Coupler OC2. The Opto coupler conducts and a level  ‘0 ’ is fed to  Pin 5 of U1 . This makes output to  Pin 6 of U1   as  ‘0’ . At the same time, since no current passes through Input Diode of OC1, it does not  conduct. Level  ‘1’  is fed to   Pin 1 of U1  and output to  Pin 3 of U1  to Port becomes  ‘0’ .This time, the inputs to Port changes to  1010 . 
 We find that Port inputs  0101 and 1010 are the valid levels . All other combinations  are  invalid levels.  
 If Hardware De-bounce Cct U1 is replaced by  Software De-bounce  to reduce Parts Count to enhance Reliability, the inputs to Port will change to  01  when Relay X is not operated and  10  when it is  operated. 
 If a vital decision is taken by   Pick-up condition of Relay X, then a failure to read Pick-up condition as Drop, is a  Safe failure . But if Drop condition is read as Pick-up condition, it will be  Unsafe failure . 
 Now we shall have to do an  Failure Mode Effects & Criticality Analysis (FMECA)   study of the Cct showed in Fig 3 and identify the  critical component to cause Unsafe Failure  and mitigate the  Hazard.  
   Failure Mode Effects & Criticality Analysis (FMECA)   
 We shall first study the failure modes of the components. For every failure mode of components , we shall their effect for Drop and Pick-up conditions. 
 Typical faults of an Electronic component are  Open Cct, Short Cct, Drift in Parameter  and  Functional Faults.  Average relative frequencies of Failure Modes of various Components are given in the Table 1 below. 
   
 Terminating Resistors and Current Limiting Resistors are of mainly  Metal Film type  for which  Short cct Mode is incredible  and hence are not considered. When Resistors are used in Nodes with  Pull up Totem-pole Driver , even  Drift in value  is  not to  be considered.  For open Collector Modes like Opto coupler output, the design ensures much higher Collector current as well as Diode input current , so that even   ± 20% Drift does not affect  the Circuit behaviour. 
 
 So, for Resistors , only Open Cct Mode  is considered. 
 For Inductors,  any Drift will not affect normal operation  and  only Open Mode  of failure is considered. 
 
 
 For Varistor,  Open Mode does not affect normal operation  and if the  Clamp Voltage is chosen much higher than the required Value , Drift also does not have any effect.  Only Short cct Mode is analysed . 
 
 
 For ICs,  both   s-a-0   and   s-a-1   Faults  are considered for every Pin. 
 
 Now we will consider  component-wise FMECA.  The effects during Relay Drop  and Pick-up conditions are analysed for each Component Failure. 
 a)   If Inductor L1 is Open   
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC1. U1 pin 1 is at ‘1’ and U1 pin 5 is  aIso ‘1’. Output  to Port will be ’1011’. Fault is detected as Invalid Data and failure is Safe.  Since both the Inputs to Debounce Cct are at ‘1’, its Output will remain at last State, i.e. 01. 
  Relay Pick-up condition : 
 Current  passes through input of Opto Coupler OC2. U1 pin 1 is at ‘1’ and U1 pin 5 is  at ‘0’. Output  to Port will be ’1010’. Fault is not detected  and failure is Safe.  
 b)   If Inductor L2 is Open   
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC2. U1 pin5  is at ‘1’ and U1 pin 1 is at ‘0’. Output  to Port will be ’0101’. Fault is not detected and failure is Safe.  
  Relay Pick-up condition : 
 Current  passes through input of Opto Coupler OC1. U1 pin 1 is at ‘1’ and U1 pin 5 is  also at ‘1’. Output  to Port will be ’1011’. Fault is  detected  as invalid data. 
   c) if Metal Oxide Varistor RV1 is Short :    
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC1. U1 pin 1 is at ‘1’ and U1 pin 5 is  aIso ‘1’. Output  to Port will be ’1101’. Fault is detected as invalid data and failure is Safe.  
  Relay Pick-up condition : 
 Current  passes through input of Opto Coupler OC2. U1 pin 1 is at ‘1’ and U1 pin 5 is  at ‘0’. Output  to Port will be ’1010’. Fault is not detected  and failure is Safe.  
   d) if Metal Oxide Varistor RV2 is Short :    
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC2. U1 pin5  is at ‘1’ and U1 pin 1 is at ‘0’. Output  to Port will be ’0101’. Fault is not detected and failure is Safe.  
  Relay Pick-up condition : 
 Current does not pass through input of Opto Coupler OC2. U1 pin 5 is at ‘1’ and U1 pin 1 is  aIso ‘1’. Output  to Port will be ’1011’. Fault is detected as invalid data and failure is Safe.  
   e) If Current Limiting Resistance R1 is Open:   
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC1. U1 pin 1 is at ‘1’ and U1 pin 5 is  aIso ‘1’. Output  to Port will be ’1101’. Fault is detected as invalid data and failure is Safe.  
  Relay Pick-up condition : 
 Current  passes through input of Opto Coupler OC2. U1 pin 1 is at ‘1’ and U1 pin 5 is  at ‘0’. Output  to Port will be ’1010’. Fault is not detected  and failure is Safe.  
   f) If Current Limiting Resistance R2 is Open:   
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC1. U1 pin 1 is at ‘1’ and U1 pin 5 is  aIso ‘1’. Output  to Port will be ’1101’. Fault is not detected data and failure is Safe.  
  Relay Pick-up condition : 
 Current  does not pass through input of Opto Coupler OC2. U1 pin 1 is at ‘1’ and U1 pin 5 is also at ‘1’. Output  to Port will be ’1011’. Fault is  detected  as invalid and failure is Safe.  
   g) If Current Limiting Resistance R5 is Open:   
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC2. U1 pin 1 is at ‘0’ and U1 pin 5 is  aI ‘1’. Output  to Port will be ’0101’. Fault is not detected data and failure is Safe.  
  Relay Pick-up condition : 
 Current  does not pass through input of Opto Coupler OC2. U1 pin 1 is at ‘1’ and U1 pin 5 is  at ‘1’. Output  to Port will be ’1010’. Fault is not detected  and failure is Safe.  
   h) If Current Limiting Resistance R6 is Open:   
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC2. U1 pin 1 is at ‘0’ and U1 pin 5 is  aI ‘1’. Output  to Port will be ’0101’. Fault is not detected data and failure is Safe.  
  Relay Pick-up condition : 
 Current  does not pass through input of Opto Coupler OC2. U1 pin 1 is at ‘1’ and U1 pin 5 is  at ‘1’. Output  to Port will be ’1010’. Fault is not detected  and failure is Safe.  
   i) If Protection Diode D1 is open:   
 Normal operation of the cct is not affected. But a reverse voltage of more than 6V during Drop condition would damage the Diode of Opto coupler OC1. During Pick-up condition, there is no effect. 
   j) If Protection Diode D2 is open:   
 Normal operation of the cct is not affected. But a reverse voltage of more than 6V would damage the Diode of Opto Coupler OC2 during Pick-up. There is no effect during  Drop condition. 
   k) If Protection Diode D1 is short:   
  Relay Drop condition:  
 Opto coupler OC1 will be OFF since current will  be bypassed via D1. U1 pin 1 is at ‘1’ and U1 pin 5 is  at ‘1’. Output  to Port will be ’1101’. Fault is detected as invalid data and failure is Safe.  
  Relay Pick-up condition : 
 Opto coupler OC1 will be OFF since current will  be bypassed via D1. U1 pin 1 is at ‘1’ and U1 pin 5 is  at ‘1’. Output  to Port will be ’1010’. Fault is not detected failure is Safe.  
   l) If Protection Diode D2 is short:   
  Relay Drop condition:  
 Opto coupler OC2 will be OFF since current will  be bypassed via D2. U1 pin 1 is at ‘1’ and U1 pin 5 is  also at ‘1’. Output  to Port will be ’ 0101’. Fault is not detected and failure is Safe.  
  Relay Pick-up condition : 
 Opto coupler OC2 will be OFF since current will  be bypassed via D2. U1 pin 1 is at ‘1’ and U1 pin 5 is  aIso ‘1’. Output  to Port will be ’1011’. Fault is detected as invalid data and failure is Safe. 
   m) If Input Diode of Opto Coupler OC1 is open:    
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC1. U1 pin 1 is at ‘1’ and U1 pin 5 is  aIso ‘1’. Output  to Port will be ’1101’. Fault is detected as invalid data and failure is Safe.  
  Relay Pick-up condition : 
 Current does not pass through input of Opto Coupler OC1. U1 pin 1 is at ‘1’ and U1 pin 5 is  at ‘0’. Output  to Port will be ’1010’. Fault is not detected  and failure is Safe.  
   n) If Input Diode of Opto Coupler OC2 is open:    
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC2. U1 pin 5  is at ‘1’ and U1 pin 1 is at ‘0’. Output  to Port will be ’0101’. Fault is not detected and failure is Safe.  
  Relay Pick-up condition : 
 Current  does not pass through input of Opto Coupler OC2. U1 pin 1 is at ‘1’ and U1 pin 5 is  also at ‘1’. Output  to Port will be ’1011’. Fault is  detected  as invalid data. 
   o) If Collector in Opto Coupler OC1 is open:    
  Relay Drop condition:  
 Due to the pull up Resistor 5, Current does not pass through input of Opto Coupler OC1. U1 pin 5  is at ‘1’ and U1 pin 1 is at ‘0’. Output  to Port will be ’0101’. Fault is not detected and failure is Safe.  
  Relay Pick-up condition : 
 Opto Coupler OC2 starts conducting  and port input becomes 0101. Fault is not detected  and failure is Safe.  
   p) If Collector in Opto Coupler OC2 is open:    
  Relay Drop condition:  
 Current does not pass through input of Opto Coupler OC2. U1 pin5  is at ‘1’ and U1 pin 1 is at ‘0’. Output  to Port will be ’0101’. Fault is not detected and failure is Safe.  
  Relay Pick-up condition : 
 Current  passes through input of Opto Coupler OC1. U1 pin 1 is at ‘1’ and U1 pin 5 is  also at ‘1’. Output  to Port will be ’1011’. Fault is  detected  as invalid data. 
   q) If Collector and Emitter of OC1 is short:    
  Relay Drop condition:  
 We get  1 in Pin 1 of U1 and port gets data 0101. Fault is not detected and failure is Safe.  
  Relay Pick-up condition : 
 Both pins 1 and 5 get 1 and we get 0110. Fault is  detected  as invalid data. 
   r) If Collector and Emitter of OC 2 is short:    
  Relay Drop condition:  
 We get  1 in Pin 5 of U1 and port gets data 1010. Fault is not detected and failure is Safe.  
  Relay Pick-up condition : 
 Both pins 1 and 5 get 1 and we get 0110. Fault is  detected  as invalid data. 
   s) If Pull up Resistor R3 is open:   
  Relay Drop condition:  
 Since Opto Coupler OC1 is in operated condition, we get  0 in Pin1 of U1 and port gets data 0101. Fault is not detected and failure is Safe.  
  Relay Pick-up condition : 
 If there is large leakage current from Supply and Ground, the Collector of Opto coupler OC1 will be at level ‘0’. So data to  port will be 0110. Fault is  detected  as invalid data. 
   t) If Pull up Resistor R7 is open:   
  Relay Drop condition:  
 Since Opto Coupler OC2 is in operated condition, we get  0 in Pin5 of U1 and port gets data 0110. Fault is detected as invalid data and failure is Safe.  
  Relay Pick-up condition : 
 If there is large leakage current from Supply and Ground, the Collector of Opto coupler OC1 will be at level ‘0’. So data to  port will be 1010. Fault is  not detected.  
   u) If S-a-0 fault is at Pin 1 of U1:    
  Relay Drop condition:  
 Pin 3 of U1 will be ‘1’ and Port Input is 0101. Fault is not detected. 
  Relay Pick-up condition : 
 Port Input will be 0110, which is invalid. 
   v) If S-a-0 fault is at Pin 5 of U1:    
  Relay Drop condition:  
 Pin 6 of U1 will be ‘1’ and Port Input is 0110 which is invalid. 
  Relay Pick-up condition : 
 :Port Input will be 1010. Fault is not detected. 
   w) If S-a-1 fault is at Pin 1 of U1:    
  Relay Drop condition:  
 Pin 1 and Pin 5 of U1 both will be ‘1’ and Port Input remains 0101. Fault is not detected. 
  Relay Pick-up condition : 
 Port Input will be 1010. Fault is not detected. 
   x) If S-a-1 fault is at U1-5:   
  Relay Drop condition:  
 Pin 6 of U1 will be ‘0’ and Port Input is 0101.  Fault is not detected. 
  Relay Pick-up condition : 
 Pin 1 and Pin 5 of U1 both will be ‘1’ and Port Input remains 1010. Fault is not detected. 
   y) If S-a-0 fault is at U1-3:   
  Relay Drop condition:  
 Pin 3 of U1 will be ‘0’ and Port Input is 0011, which is invalid. 
  Relay Pick-up condition : 
 Port Input is 1010. Fault is not detected. 
   z) If S-a-0 fault is at U1-6:   
  Relay Drop condition:  
 Port Input is 0101. Fault is not detected. 
  Relay Pick-up condition : 
 Port Input is 1100, which is invalid. 
   aa) If S-a-1 fault is at U1-3:   
  Relay Drop condition:  
 Port Input is 0101. Fault is not detected. 
  Relay Pick-up condition : 
 Port Input is 1101, which is invalid. 
   ab) If S-a-1 fault is at U1-6:   
  Relay Drop condition:  
 Port Input is 0111, which is invalid. 
  Relay Pick-up condition : 
 Port Input is 1010. Fault is not detected. 
   ac) If R4 is Open:   
  Relay Drop condition:  
 LED 1 will not glow. Since LED 2 also does not glow, fault can be usually detected. 
  Relay Pick-up condition : 
 Since LED 2 glows, fault cannot be detected. 
   ad) If R8 is Open:   
  Relay Drop condition:  
 Since LED 1 glows, fault cannot be detected. 
  Relay Pick-up condition : 
 LED 2 will not glow. Since LED 1 also does not glow,  fault can be usually detected . 
   ae) If LED1 is faulty:    
  Relay Drop condition:  
 LED 1 will not glow. Since LED 2 also does not glow,  fault can be usually detected.  
  Relay Pick-up condition : 
 Since LED 2 glows, fault cannot be detected. 
   af) If LED2 is faulty:    
  Relay Drop condition:  
 Since LED 1 glows, fault cannot be detected. 
  Relay Pick-up condition : 
 LED 2 will not glow. Since LED 1 also does not glow, fault can be usually detected. 
 In summary,  Invalid Input  is obtained in  Relay Drop  condition if 
 
  OC1 Output is Short  
  OC2 Input or Output is Open  
  U1-3 S-a-1  
  U1-6 S-a-0  
 
 Similarly,  Invalid Input  is obtained in  Relay Pick-up   condition if 
 
  OC1 Input or Output is Open   
  OC2 Output is Short  
  U1-3 S-a-0  
  U1-6 S-a-1  
 
 It also shows that a  single fault cannot lead to Unsafe Failure.  
 After the completion of FMECA, we are to perform  Fault Tree Analysis (FTA)  of the Circuit to identify the  causes of Safe and Unsafe Failures .                                  
                           Fault Tree Analysis (FTA)   
 We shall now learn how the Circuit can fail to operate. So, we shall make a Fault Tree Analysis as shown below. Fault trees are individually made for both Safe as well as Unsafe Failures. 
 Safe Failure can occur due to Two simultaneous Faults ---  Open Cct   Fault in Opto Coupler   OC2  as well as Short Cct  Fault in Opto Coupler OC1.  Unsafe Failure can occur due to Two simultaneous Faults ---  Open Cct Fault in Opto Coupler OC1  as well as Short Cct  Fault in Opto Coupler OC2.        
   
 Unsafe Failure can happen only due to simultaneous Faults in  Open cct in Relay NO path  and  Short cct in Relay NC path.  
           CCT UNSAFE FAILURE (0101 is read as 1010)   
       
                Once we prepare the Fault Tree, we are to calculate the  Failure Rate of the Card . 
               For this, we are initially to find the Basic Failure Rate for each component as per Calculations given in  MIL Std 217F . Then we are to Calculate the  actual Failure Rate  under environmental stress. 
    The environmental stress factors are : 
  λ C  =  Contact Constitution Factor  
  λ Q  = Quality Factor  
  λ E  =  Environmental Factor. We consider Ground Fixed  
  λ T  =  Temperature Factor  
  λ s  =  Electrical Stress Factor  
  λ R  =  Resistor Value factor  
  λ CV  = Capacitor Value Factor  
    Typical Calculations for a Components are showed in Chapter. The following Table shows the individual Component Failure Rates for the Input Interface Cct. 
   
 We have seen that Unsafe Failure can be caused only by 2 simultaneous failures –  Open Circuit in OC 1  and  Short Circuit of OC 2   Output.  So, the Failure Rate will be the  Product of Individual Failure Rates  of the 2 Opto Couplers. From the table above, we find that the Failure Rate of an Opto Coupler is  0.0257 X 10   -6   .  So, the  Unsafe Failure Rate  will be ( 0.0257 X 10   -6  )  2    = 6.6040    X 10  -16.    This is far above the  requirement of SIL 4.  Total Failure Rate of the Card is  3.375477 X   10   -6   giving a  Mean Time Between Failure  of  296254.4 Hours.   
  Reliability  after a period of  One year (8760 Hrs) i s    
  R =   e      – λt   
          =   e   -  0.0000033754 X 8760   
     = e   –  0.029568   
     =       0.97086  
     Designed Life  with  99% Reliability   
  = (- ln 0.99) / 0.0000033754  
  = 0.01005033585 / 0.0000033754  
  = 2977.5 Hrs.  
   Preventing Common- Mode Failures:   
 To reduce Common- mode failures, we can feed  U1 outputs in two different Ports  and that too  at different Input Pins . For example, if  Pin 3 of U1  is fed to  D0 of Port A,   Pin 6 of U1  should be fed to  D7 of Port B . Then we can  match them through Software  in Processor Card. See the Diagram of the connection in  Fig 4  
     
 A Program for the same task is written below in 8085 Assembly language. 
  START:           IN Port 1                      :    Read  Drop Contact Data  
                        MOV D, A                   :    Save Data 
                         IN Port 2                      :    Read  Pick-Up Contact Data  
  MATCH:         PUSH D                      :     Save  Drop Contact Data 
                        CMA                            :     Invert  Pick-Up Contact Data 
                        MOV B, A                   :    Save Data 
                        MVI C,  00                    :    Initialize  Register ‘C’ 
                        LXI H,  0180                 :    Initialize  Registers : ‘H’ and ‘L’ 
                        MVI E, 08                   :    Load  Count (8) for the Loop Iterator  
  LOOP  :          ANA H                         :    Mask Unconcerned Bits of the  Pick-Up* Data   
                        JNZ  ONE                     :    If Data Bit is Not 0,  Go to Label ONE  
                         MOV A, L                    :    Transfer Data from Register ‘L’ to ‘A’. 
                         CMA                            :     Invert  Data of Accumulator 
                         ANA C                         :    Mask Unconcerned Bits 
                         JMP  ZERO                  :     Go To Label ZERO . 
  ONE    :          MOV A, C                   :     Copy  Contents of ‘C’ to Accumulator 
                       ORA L                         :    Make  MSB ‘1’  and progress with other bits 
  ZERO  :          MOV C, A                   :    Save the new value in Register C 
                      MOV A, H                   :    Load  Bit Position Indicator  in Accumulator 
                      ADD H                        :    Shift Left for  Next Bit indicator  
                        MOV H, A                   :    Save the Bit Indicator Data.                
                      MOV A, L                    :    Load Bit Position in Accumulator         
                    RRC                            ;    Go to  Next Bit Position  
                        MOV L, A                 :    Save Updated Bit Position Data 
                        MOV A, B                 :    Read  saved Pick-up* Contacts Data  
                        DCR E                     :    Check for  completion of all 8 Bits  
            JNZ LOOP             :  Repeat  Rearranging  for all 8 Bits  
                         MOV A, C               :   Save Rearranged Pick-up* Data 
                         POP  D                   :  Restore  Saved Drop Contact Data 
                         RET                       :   Go back to Main Programme 
                        CMP D                    :   Compare Drop  and  Pick-up* Data  
                       JNZ FLT                 :   If not Matched,  Go to  Fault  
 This Subroutine is Executed in  34.5 μs,  considering that each State in 8085 generally takes  330 ns for execution . 
      Toggling of Input data     to detect Opto Coupler Faults   
 Instead of keeping the Emitter of Opto Coupler permanently Grounded, we feed ‘0’ from Processor through Port C of Programmable Peripheral Interface 8255, to the Emitters as showed in Fig  5.  
     
     
 After reading the input and analysing, we momentarily feed ‘1’ to the Emitters. Now, all the opto-couplers  should be OFF.  That means, Opto-coupler outputs should follow the  Toggling input  from the microprocessor. Now, we again feed ‘0’ from the Processor and analyse the Opto-coupler Outputs finally. 
 We take inputs from Drop Contacts of 4 different relays along with the Output of U1 Pin 3 of their De-bounce circuits, via Port ‘A’ of 8255. Similarly, the pick-up Contacts of the same four Relays and Output from U1 Pin 6 are taken through Port ‘B’. For 16 relays, Interface to the Card, 4 numbers of 8255 ICs  PPI 8255    1 are needed. 
 The Programme for the Toggle Operation is given below: 
     
  MVI A, 92                 Programme Four PPIs (8255) having       
  OUT 03                           PORT A -- INPUT  
  OUT 07                           PORT B -- INPUT  
  OUT 0B                          PORT C -- OUTPUT  
  OUT 0F                             
 LXI H,  1100                Starting Location to keep Drop Contacts Data 
 SUB A                       Enable  Opto Couplers in PPI 1  
  OUT 02  
  IN 00                          Read  Drop contact Status  from  PPI 1  
 MOV M, A                 Save in  Location 1100  
  IN 01                          Read  Pick-up contact Status  from  PPI 1  
  CALL MATCH          Rearrange Bits  and  Match them.  
 INX H                        Go to  Next Location  
 SUB A                       Enable  Opto Couplers in   PPI 2  
  OUT 06  
  IN 04                         Read  Drop contact Status  from  PPI 2  
 MOV M, A                Save in  Location 1101  
 IN 05                        Read  Pick-up contact Status  from  PPI 2  
  CALL MATCH         Rearrange Bits  and  Match them.  
 INX H                       Go to  Next Location  
 SUB A                      Enable  Opto Couplers in PPI 3  
  OUT 0A  
  IN 08                         Read  Drop contact Status  from  PPI 3  
 MOV M, A                Save in  Location 1102  
  IN 09                         Read  Pick-up contact Status  from  PPI 3  
  CALL MATCH         Rearrange Bits  and  Match them.  
 INX H                       Go to  Next Location  
 SUB A                      Enable  Opto Couplers in PPI 4  
  OUT 0E  
  IN 0C                         Read  Drop contact Status  from  PPI 4  
 MOV M, A                Save in  Location 1100  
  IN 0D                         Read  Pick-up contact Status  from  PPI 4  
  CALL MATCH         Rearrange Bits  and  Match them.  
     
                           STA 1100                 Bring  Drop Contact Data  from  Location 1100  
 LXI H , 1200              Initialize  Flag Location  for  First Relay  of  PPI 1  
  IN 00                        Read  Drop contact Status  from  PPI 1          
 CPI  55                      Check if this Data is  same as the Saved Data  
  JZ PPI 2  
  CALL DELAY 1ms  Wait for 1 milli second  
 MVI A, FF                  Disable  Opto Couplers 
  OUT 02  
  IN 00  
  CALL DELAY 1ms  Wait for 1 milli second  
 CPI  FF  
  JNZ FLT                    If not,  Go to Fault  
 SUB A                      Again  Enable  Opto Couplers 
  OUT 02  
  IN 00  
 CPI  55  
  CNZ PROCESS  
  PPI   2    :             STA 1101                    Bring  Drop Contact Data  from  Location 1101  
 LXI H , 1204                  Initialize  Flag Location  for  First Relay  of  PPI 2  
  IN 04                            Read  Drop contact Status  from  PPI 2  
 CPI  AA  
  JZ PPI 3  
  CALL DELAY 1ms     Wait for 1 milli second  
 MVI A,  FF                    Disable  Opto Couplers 
  OUT 06  
  IN 04                            Read  Drop contact Status  from  PPI 2  
  CALL DELAY 1ms     Wait for 1 milli second  
 CPI  FF                        Check if Opto Couplers are Disabled  
  JNZ FLT                      If not,  Go to Fault  
 SUB A                        Again  Enable  Opto Couplers 
  OUT 06  
  IN 04                           Read  Drop contact Status  from  PPI 2  
 CPI  AA  
  CNZ PROCESS  
  PPI 3       :        STA 1102                   Bring  Drop Contact Data  from  Location 1102  
 LXI H , 1208                Initialize  Flag Location  for  First Relay  of  PPI 3  
  IN 08                          Read  Drop contact Status  from  PPI 3  
 CPI  55                     
  JZ PPI 4  
  CALL DELAY 1ms   Wait for 1 milli second  
 MVI A, FF 
  OUT 0A  
  IN 08                          Read  Drop contact Status  from  PPI 3  
  CALL DELAY 1ms   Wait for 1 milli second  
 CPI  FF                      Check if Opto Couplers are Disabled  
  JNZ FLT                    If not,  Go to Fault  
 SUB A                       Again  Enable  Opto Couplers 
  OUT 0A  
  IN 08                         Read  Drop contact Status  from  PPI 2  
 CPI  55  
  CNZ PROCESS  
  PPI   4    :             STA 1103                 Bring  Drop Contact Data  from  Location 1104  
 LXI H , 120C              Initialize  Flag Location  for  First Relay  of  PPI 4  
  IN 0C                        Read  Drop contact Status  from  PPI 4  
 CPI  AA     
  JZ NXT_CARD  
  CALL DELAY 1ms  Wait for 1 milli second  
 MVI A,  FF                 Disable  Opto Couplers 
  OUT 0E  
  IN 0C                         Read  Drop contact Status  from  PPI 4  
  CALL DELAY 1ms  Wait for 1 milli second  
 CPI  FF                       Check if  Opto Couplers are Disabled  
  JNZ FLT                    If not,  Go to Fault  
 SUB A                       Again  Enable  Opto Couplers 
  OUT 0E  
  IN 0C                          Read  Drop contact Status  from  PPI 4  
 CPI  AA  
  CNZ PROCESS  
     
  PROCESS   :    MOV B, A    
     MVI C,  04  
                MVI D,  40                                
  CHK             :     MOV B, A 
                 ANA D 
                JNZ PICK-UP  
               MVI A, FF 
                 MOV M, A 
  PICK-UP       :   MOV A, D 
 RLC 
 MOV D, A 
 ANA D 
  JNZ FLT  
 SUB A 
 MOV  M, A 
 INX H 
 MOV A, D 
 RLC 
 MOV D, A 
 DCR C 
  JNZ CHK   
     dELAY 1  ms :   PUSH D  
  BACK           :    LXI B , 0BB1  
                             DCX B 
  JNZ BACK  
 POP D 
 RET 
  This Programme to check the Status of the Relays Interfaced in One Card takes about  9.64 ms . Thus to check all 16 Input Cards, a total time of  154 ms  is needed. It covers up the  Transition periods for QN1 Relays.  
   Card AcCcess   
 Whenever an Input Card is inserted into one of the I/O Slots, it gets the  I/O Slot address , which is  Hardwired in Back-plane . Processor Card sends  Motherboard Slot addres s through the I/O Bus. When the two addresses match, the Comparator Output Pin gets low and a Decoder and Data Buffer are enabled. The arrangement is showed in  Fig 6 . 
   
      
 The FMECA of this sub- circuit is given below. 
   a) If Pin 19 of Comparator UA is s-a-1:    
 The Decoder UD and Buffer UC will not be enabled. Processor cannot read ID andID* of Input Card. 
   b) If pin 19 of Comparator UA is s-a-0:    
 The fault will not be detected. 
   c) If any Input Pin of P or Q Comparator of UA is     s-a-0 / s-a-1    :   
 Software data sent by Processor will not match with Hardware data from the Backplane. Failure is same as (a). 
   d) If any Pull- up resistor for Backplane is Open:   
 The corresponding Pin may float to either 0 or  1. Depending on that the Hardware and Software addresses may or may not match. 
   e) If any Input Pin of Buffer UB is     s-a-0 or s-a-1.   
 Software data will be faulty and may or may not match with Hardware data. 
   f) If Pin 19 of Bus Driver UC is     s-a-1:   
 UC will not be enabled. Card ID and ID* cannot be read. 
 g)   f) If Pin 19 of Bus Driver UC is     s-a-0    :   
 UC will be permanently enabled and the fault will remain undetected while accessing the Card. 
   h) If Pin 1of Bus Driver UC is     s-a-1    :   
 UC will not allow reading Card ID and ID*. 
   i) if any Data Pin of Bus Driver UC is     s-a-0 or s-a-1  : 
 Processor will get wrong ID and ID*. 
   j) If Pins 1 and 19 of Buffers UE or UF are     s-a-1    :   
 Processor will not get  ID or ID*  depending on whether  UE or UF  has got the fault. 
   j) If Pins 1 and 19 of Buffers UE or UF are     s-a-0    :   
 UE or UF will be permanently enabled . There will be Bus contention while reading ID and ID*.